Example dossier

Villa des Érables, from plan to dossier

A two-storey house with a garage, drawn and wired in ES Schémas: 13 rooms, 2 boards, 21 circuits. Here is its dossier sheet by sheet, and what the RGIE checks make of it. The client, address and site are fictitious.

2levels
13rooms
2boards
21circuits
78devices
13A4 sheets

The RGIE checks at work

The same house, with eight common mistakes

To show the checks at work, we took the Villa des Érables and slipped in mistakes you come across on site. ES Schémas finds every one, cites the RGIE clause and takes you to the item concerned.

8to fix
10to check
317compliant
  • ID5 · RCD typeType AC RCDs are no longer allowed: RCDs in domestic installations are at least type A.To fix · 5.3.5.3 a
  • O · 30 mA RCDThis circuit supplies socket outlets not intended for a fixed appliance and a bathroom or shower: no RCD of 30 mA at most protects it, whereas one is required downstream of the main RCD. Circuits at SELV or with electrical separation are exempt.To fix · 4.2.4.3 b; 7.1.4.3
  • P · 30 mA RCDThis circuit supplies a bathroom or shower: no RCD of 30 mA at most protects it, whereas one is required downstream of the main RCD. Circuits at SELV or with electrical separation are exempt.To fix · 4.2.4.3 b; 7.1.4.3
  • ID3 · protected circuits11 final circuits downstream: 8 at most per 30 mA RCD.To fix · 4.2.4.3 b
  • A · cross-section and protectionA 20 A circuit breaker exceeds the 16 A allowed for 1.5 mm².To fix · 4.4.1.4, table 4.11
  • D · cross-section and protectionA 32 A circuit breaker exceeds the 20 A allowed for 2.5 mm².To fix · 4.4.1.4, table 4.11
  • B · number of sockets9 single or multiple socket outlets on this final circuit: at most 8 per final circuit.To fix · 5.3.5.2 b
  • E · dedicated circuitElectric oven shares this circuit with other loads: a fixed appliance of 2600 W or more (3500 W) is supplied separately by a dedicated circuit.To fix · 5.2.1.2
Checks · version to correct
The ES Schémas Checks page on the version to correct: eight findings to correct, each with its RGIE clause.
0to fix
8to check
312compliant

And once corrected

The published version of the dossier has nothing left to correct. 8 points remain “to check” that only an on-site inspection can settle: bathroom zones, earth electrode and equipotential bonding, boards, EV charger installation, and the qualifications of the person in charge of the work.

Yours could be next

Open the Villa des Érables in ES Schémas, or start your own project: 30-day free trial, no credit card.